System model |
RP502U250L | RP502E200L |
|
System information |
|
|
Nominal AC power |
250 kW | 200 kW |
|
Nominal capacity |
502 kWh |
|
Battery Information |
|
|
Battery chemistry |
LFP |
|
Capacity |
280Ah |
|
Configuration |
280S2P |
|
Nominal voltage |
896V |
|
Voltage range |
784~1000V |
|
Inverter information |
|
|
Max. AC power |
2 x 125kW | 2 x 100kW |
|
Nominal Grid/Islanding Voltage |
480V | 400V |
|
Grid voltage range |
422.4V~528V | 320~456V |
|
Power factor |
-1~1, continuously adjustable |
|
Nominal grid frequency |
60Hz | 50Hz |
|
Isolation |
Transformerless |
|
Working conditions |
|
|
Degree of protection |
NEMA 3R / IP54 |
|
Noise emission |
≤72dB @1m |
|
Operating temperature range |
-22°F ~ 113°F / -30°C ~ 45°C |
|
Relative humidity |
0~95% (No condensing) |
|
Max. working altitude |
6,500ft / 2,000m |
|
General data |
|
|
Dimensions (W*H*D) |
14.9'×8.2'×5.2’/ 4,550×2,500×1,600mm |
|
Weight (with & without batteries) |
15,500lbs & 6,600lbs / 7t & 3t |
|
Cooling Method of Battery Chamber |
HVAC |
|
Fire Suppression System |
FM200 (Novec 1230 optional) |
|
Communication Protocol |
Modbus TCP/IP |
|
Certificate |
UL1741, UL 1741SA, IEEE1547, UL1973, UL9540A, UL9540 | IEC62619, IEC61000, IEC62477, G99, AS4777.2 |